Steel Column Validation Examples
Parameter | Values (Grade 50 / Grade 65) |
---|---|
Axial Loads | D = 140 kips, L = 420 kips |
Length | 30’ |
Yield Strength | 50 ksi / 65 ksi |
Section Size | W14x132 / W14x120 |
Value | Example (Gr. 50 / Gr. 65) | ClearCalcs (Gr. 50 / Gr.65) |
---|---|---|
Factored Load | 840 kip | 840 kip |
Available Strength | 893 kip / 856 kip | 893 kip / 856 kip |
Parameter | Values |
---|---|
Axial Loads | D = 6 kips, L = 18 kips |
Length | 20’ |
Yield Strength | 50 ksi |
Section Size | WT7x15 |
Value | Example | ClearCalcs |
---|---|---|
Applied Load | 24 kip | 24 kip |
Elastic Flexural Buckling Stress (X-Axis) | 21.3 ksi | 21.3 ksi |
Elastic Flexural Buckling Stress (Y-Axis) | 11.0 ksi | 11.0 ksi |
Elastic Flexural-Torsional Buckling Stress | 10.5 ksi | 10.5 ksi |
Critical Buckling Stress | 9.21 ksi | 9.21 ksi |
Effective Area | 4.42 in2 | 4.42 in2 |
Available Compressive Strength | 24.4 kip | 24.4 kip |
Parameter | Values |
---|---|
Length | 24’ |
Yield Strength | 50 ksi |
Section Size | HSS 12 x 8 x 3/16 |
Value | Example | ClearCalcs |
---|---|---|
Critical Buckling Stress | 29.1 ksi | 29.1 ksi |
Effective Area | 5.77 in2 | 5.7 in2 * |
Available Compressive Strength | 101 kip | 99.4 kip |
Parameter | Values |
---|---|
Axial Loads | D = 5 kip, L = 15 kip |
Lateral Loads (X-Axis) | wD = 0.612 kip/ft, wL = 1.837 kip/ft |
Lateral Loads (Y-Axis) | wD = 0.08163 kip/ft, wL = 0.2449 kip/ft |
Length | 14’ |
Yield Strength | 50 ksi |
Section Size | W10x33 |
Value | Example | ClearCalcs |
---|---|---|
Factored Axial Load | 20 kip | 20 kip |
Unamplified Moment (X-Axis) | 60 kip*ft | 60 kip*ft |
Unamplified Moment (Y-Axis) | 8 kip*ft | 8 kip*ft |
Available Axial Strength | 168 kip | 168 kip |
Amplified Moment (X-Axis) | 61.2 kip*ft | 61.1 kip*ft |
Amplified Moment (Y-Axis) | 8.72 kip*ft | 8.76 kip*ft |
Available Flexural Strength (X-Axis) | 91.0 kip*ft | 90.7 kip*ft |
Available Flexural Strength (Y-Axis) | 34.9 kip*ft | 34.9 kip*ft |
Interaction Check | 0.982 | 0.984 |
Parameter | Values |
---|---|
2nd Floor Loads | D = 12.2 kips, L = 2.88 kips |
3nd Floor Loads | D = 12.5 kips, L = 2.88 kips |
Roof | D = 4.59 kips, L = 3.6 kips |
Length | 10.67 ft |
Yield Strength | 42 ksi |
Section Size | HSS5.563X0.134 |
Value | Example (LRFD / ASD) | ClearCalcs ( LRFD / ASD) |
---|---|---|
Factored Axial Load (LRFD) or (ASD) | 46.7 kip / 36.3 kip | 46.7 kip / 36.3 kip |
Factored Available Strength (LRFD) or (ASD)* | 61 kip / 40.6 kip | 61 kip / 40.6 kip |
Effective Area | 2.12 in2 | 2.12 in2 |
Critical Flexural Buckling Stress / ** | 31.97 ksi | 32.0 ksi |
Parameter | Values |
---|---|
Axial Loads | D = 300 kip, L = 200 kip, Wdn = 640 kip |
Lateral Loads | Wdn = 240 kip at 13.5 ft |
Length | 27 ft |
Yield Strength | 50 ksi |
Weak Axis Support Locations | 9 ft, 18 ft |
Section Size | HSS5.563X0.134 |
Value | Example | ClearCalcs |
---|---|---|
Factored Axial Load | 1100 kip | 1100 kip |
Factored Compression Strength | 2223 kip | 2220 kip |
Factored Flexural Strength | 3259 kip | 3260 kip |
Compression - Bending Interaction | 0.949 | 0.949 |